Data and Installation S4 Mains powered interface unit
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk
Telephone: +44 (0) 116 246 2000 Tech. Support: www.gentexpert.co.uk Fax (UK): +44 (0)116 246 2300
4 4188-968 issue 2_Part 1_09-10_S4 mains interface
by Honeywell
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
Do not dispose of with your normal household waste.
Do not burn.
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
External wiring
Options
These optional products should be mounted on the DIN rail.
&
The relays and intrinsically safe products listed below should be mounted apart, a metal screen is
provided inside the enclosure.
19104-52 Low voltage power relay
17740-20 Intrinsically safe galvanic isolator for IS detectors and call points
02518-10 Intrinsically safe galvanic isolator for IS sounders
PB1
0C LC 01
L1
02
L2
LOOP
LOOP OUT
LOOP IN
LOOP
COMMON
PB6
++--
AUX O/P
External
Equipment
PB2, PB3,
PB4orPB5
S+ S-
SECTOR1,2,3or4
LED Output
PB2, PB3,
PB4orPB5
S+ S-
SECTOR1,2,3or4
10K EOLW
IS Sector Output
IS Galvanic
isolator (02518-10)
PB2, PB3,
PB4orPB5
Z+ Z-
ZONE 1, 2, 3 or 4
22uF EOL
Zone Input
PB2, PB3,
PB4orPB5
Z+ Z-
ZONE 1, 2, 3 or 4
5K6 EOL
IS Zone Input
PB2, PB3,
PB4orPB5
S+ S-
SECTOR1,2,3or4
10K EOLW
Sector Output
with Sounders
PB2, PB3,
PB4orPB5
S+ S-
SECTOR1,2,3or4
10K EOLW
Flyback
diode
Sector Output
with Inductive
load (eg Relay)
PB2, PB3,
PB4orPB5
Z+ Z-
ZONE 1, 2, 3 or 4
470R EOL
Switch Input
470R
IS Galvanic
isolator (17740-20)
Auxiliary Output:
12V# or 24V @ 0.5A
# - for S43440-12 only
11+
12-
1+
2-
12
11
2
1
Connected to
metal enclosure
End-of-line units
Capacitor 22uF
Resistor 470W
yellow, violet, brown
Resistor 5K6KW
green, blue, red
Resistor 10KW
Brown, black, orange
It is possible to
connect a number of
LEDs in series
(current is 1.5mA.
To avoid damage to equipment always
configure the interface inputs and
outputs before connecting the external
circuits.
Intrinsically
safe devices
Normally closed contacts
should be used for
fail-safe applications.
Intrinsically
safe devices
cable length
max.50m
cable length max.150m
cable length max.150m
cable length max.150m
cable length
max.50m
cable length
max.150m
cable length
max.150m
www.acornfiresecurity.com