S9240F2051 MODULATING INTEGRATED FURNACE CONTROL
69-2807—01 4
.
4-position screw terminal block
(#5 screw)
Outdoor Sensor
(optional)
E4
If used: Outdoor air sensor
Discharge Air Sensor
(optional)
If used: Discharge air sensor
Straight Spade Quick Connect Flame Sense E42 Flame signal input
4-position screw terminal block
(#5 screw)
R
OUTDOOR
EQUIPMENT
24 Vac supply from transformer
I + Communication High connection
I - Communication Low connection
C Common 24 Vac return to transformer
4-position screw terminal block
(#5 screw)
R
INDOOR
EQUIPMENT
24 Vac supply from transformer
I + Communication High connection
I - Communication Low connection
C Common 24 Vac return to transformer
2-position screw terminal block
(#5 screw)
I + (optional)
E33
Auxiliary Communication High connection
I - (optional) Auxiliary Communication Low connection
12-pin connector (male terminals) Main Harness
J2
Main valve, pressure switches, rollout, limit,
chassis ground, and 24 Vac
6-pin connector (male terminals) Circulator Motor
P79
Motor serial control interface and furnace size
select input
Table 2. Wiring Connections - Class 1 - Line Voltage. (Continued)
Terminal Type Connection/Label
Board label
(see Fig. 1) Connects S9240F to:
2 pin connector (male terminals) Igniter P77 – HSI Igniter interface
3-pin connector (male terminals) CAI Connector J3 – CAI 3-phase AC power
Straight Spade Quick-connect Humidifier HUM Humidifier 120 Vac output
EAC EAC Electronic air cleaner 120 Vac output
L1 connectors E34, E35, and
E41
Any L1 connector can be used for
120 Vac Main input
Transformer 120 Vac output
Circulator 120 Vac output
Neutrals E36, E37,
E38, E39,
and E40
Any neutral connector can be used for:
120 Vac Input neutral
Transformer neutral
Electronic air cleaner neutral
Circulator neutral
Humidifier neutral
Table 3. Jumpers.
Jumper
Board label
(see Fig. 1) Action:
W915 - 2-Stage Compressor W915 UNCUT: Single stage compressor (factory default)
CUT: 2-stage compressor
W951 - Heat Pump W951 UNCUT: Compressor heating disabled (factory default)
CUT: Compressor heating enabled
W914 - Dehumidifier W914 UNCUT: Dehumidifying operation disabled
(factory default)
CUT: Dehumidifying operation enabled
Table 1. Wiring Connections - Class 2 - Low Voltage. (Continued)
Terminal Type Connection/Label
Board label
(see Fig. 1) Connects S9240F to: