5895XL Manual - P/N 151142-L8:L 08/09/2017 11
Calculating Current Draw and Standby Battery Before You Begin Installing
6815 SLC Expander (63 max.) Standby/Alarm: 78 mA mA mA
6860 Remote LCD Annunciator (16 max.) Standby: 25 mA mA
Alarm: 50 mA mA
5860 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
6855 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
5824 Serial/Parallel I/O Module (4 max.) Standby/Alarm: 45 mA mA mA
5895XL Power Supply (16 max.) Standby/Alarm: 10 mA mA mA
5496 NAC Expander Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Standby: 35 mA mA
Alarm: 145 mA mA
5880 I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
EVS-50W or EVS-125W Audio
Amplifier with/without EVS-CE4
(4 max.) Standby: 10 mA mA
Alarm: 10 mA mA
EVS-INT50W Internal Amplifier (4 max.) Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
EVS-VCM Voice Control Module (1 max.) Standby: 70 mA mA
Alarm: 100 mA mA
EVS-SW24 Switch Expander (5 max.) Standby: 10 mA mA
Alarm: 25 mA mA
EVS-RPU Remote Paging Unit (4 max.) Standby: 70 mA mA
Alarm: 100 mA mA
EVS-LOC Local Operating Console
(includes 6860, RVM & SW-24)
(4 max.) Standby: 100 mA mA
Alarm: 150 mA mA
EVS-100W 100W amplifier (4 max.) Standby/Alarm: 10 mA mA mA
EVS-100WBU backup daughter card (4 max.) Standby/Alarm: 10 mA mA mA
Total System Current
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA mA mA
Wireless Modules
WSK-WGI Wireless Gateway Max current using ext supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
Auxiliary Devices
4
Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
Standby
Current
Alarm
Current