6820EVS Basic Operating Instructions
These instructions must be framed and displayed next to the 6820EVS panel in accordance with
NFPA 72 fire code for Local Protected Fire Alarm Systems
FS= Fire System EVS = Emergency Voice System
Operation Task to Perform
Silence Alarms and
Troubles
Press SILENCE then enter a code if prompted. Silence LED will light.
Reset Alarms
1. Press RESET.
2. Press 1 to Reset Fire System.
3. Press 2 to Reset Emergency System.
Note: To reset EVS at an LOC, the user must gain EVS Control. (See Figure 1).
View all active alarms,
troubles, and
supervisories signals
The highest priority event will display first. Press the Down arrow to view location and type of alarm or
trouble.
View a Point’s Status
1. Press ENTER to access Main Menu.
2. Press 2 to select Point Functions.
3. Then press 2 to select Point Status.
4. Select the module the device is located on by using the Up or Down button. Then press ENTER.
5. Enter the point number.
Conduct a Fire Drill
1. Press ENTER to access Main Menu.
2. Then Press 1 to select System Tests.
3. Press 1 to select Fire Drill.
4. Press ENTER to start the fire drill.
5. Press ENTER to end the fire drill.
Set Time and Date
1. Press ENTER to access Main Menu.
2. Then press 4 to select Set Time & Date. Enter a code if prompted
3. Make changes in the fields on the screen as necessary.
4. Press ENTER if you wish to keep the changes.
5. Press ENTER to set the entered time and date.
Enable / Disable a Point
1. Rotate the key or enter a code to access to access Main Menu.
2. Press 2 to select Point Functions.
3. Press 1 for Disable / Enable Pt
4. Press 7 for Disable / Enable Pt.
5. Use the Up or Down button to move through the list. Then press ENTER to select the module where
the point you want to disable/enable is located
6. Enter the point or circuit number that you want to disable/enable.
7. Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
To Gain / Request EVS
Control
1. Press the Button and follow the on-screen Instructions.
Note: When EVS Control LED is blinking, another LOC has EVS Control. EVS Control LED is on steady
when the LOC has EVS Control.
For Service Call:

Other manuals for Honeywell Silent Knight 6820EVS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Silent Knight 6820EVS and is the answer not in the manual?

Honeywell Silent Knight 6820EVS Specifications

General IconGeneral
Operating Temperature32°F to 120°F (0°C to 49°C)
TypeFire Alarm Control Panel
NAC Circuits2
Battery Backup24 VDC
Signaling Line Circuits (SLC)1
Standby Current150 mA
Humidity Range10% to 93% non-condensing
Auxiliary Power Output24 VDC, 500 mA