33
Commissioning
NOTE: If you select WIPE Config, the panel will return to the factory settings and all the existing settings will 
be deleted automatically.
Panel Description Blank 20 character 
text
Configure text for Pane Description to 
be used.
Phone Number Blank 20 character 
text
Configure phone number of service/ 
maintenance provider.
Service Date 01 Jan 2000 Date  Set service date based on agreed main-
tenance schedule. User can view this 
information along with the Site Name 
Reference and phone number of the 
service provider.
No. of Fault Polls 4 4,5,6 Number of consecutive polls required 
before device faults are reported.
This setting applies to: DEVICE LEVEL 
FAULT, DOUBLE ADDRESS FAULT, NO 
REPLY FROM DEVICE, BAD DEVICE 
REPLY, DEVICE ADDED, DEVICE NOT 
SUPPORTED, DEVICE TYPE CHANGED. 
Device Blinking ON ON / OFF Determines if the detector’s LED flashes 
when the device is polled by the panel.
Access Timeout 10 Mins 00 
Sec
0 - 60 Mins After Access Timeout period, screen 
automatically logout and navigated 
back to the main screen.
Log Diagnostic OFF ON / OFF When set as ON, false alarm suppres-
sion algorithms are by-passed for faster 
reporting of events.
Printer ON ON / OFF Allows printing of the events reported in 
the panel via an external printer, which 
can be connected to the RS232 port of 
the panel.
Table 6: Default Panel Settings
Option Title Default
Setting 
Options
Description