69-0964–2
6
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Table 4. Installer Self-Test Options.
M4864
M4865
Key to
Press
Test
Mode
Number Description
Heating Equipment Self-Test
i
10 Enter heating equipment Self-Test.
▲ 11 Stage-one heat comes on. When Installer Setup mode number 01 is 01 or mode number 02
is 01, the system fan is also energized.
▲ 12 Stage-two heat comes on. Stage-one heat and system fan remain on.
▲ 13 Stage-three heat comes on (heat pump configuration). Stage-one and stage-two heat remain
on.
▼ 12 Stage-three heat turns off.
▼ 11 Stage-two heat turns off.
▼ 10 Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select Q7100C Subbase models)
i
20 Change from heating to emergency heating equipment Self-Test.
▲ 21 Emergency heat comes on.
▼ 20 Emergency heat turns off.
Cooling Equipment Self-Test
i
30 Change from heating or emergency heating to cooling equipment self-test.
▲ 31 Stage-one cooling and system fan come on.
▲ 32 Stage-two cool comes on. Stage-one cool and system fan remain on.
▼ 31 Stage-two cool turns off.
▼ 30 Stage-one cool and system fan turn off.
Fan Equipment Self-Test
i
40 Change from cooling to fan equipment Self-Test.
▲ 41 Fan comes on.
▼ 40 Fan turns off.
KEY TEST
a
i
60 Displays 2.
▲ 60 Displays 4.
▼ 60 Displays 3.
Override 60 Displays 5.
System
a
60 Displays 0.
Fan
a
60
Displays 1.
a
Available on select models.
Thermostat Information
1. Press the Information i key to access the thermo-
stat information.
2. Press the increase ▲ key to display the production
date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 026 = February 1996)