9 63-4038—7
T7200/T7300/Q7300
INSTALLATION
TABLE 6—TERMINAL DESIGNATIONS.
a
Q7300G only.
b
Shielded cable can be required in some installations where electrical interference (noise) can cause control problems.
Standard
Terminal
Designation
Alternate
Designations Or
Customer Specials Typical Connection Function Terminal Type
BHeating damper motor; changeover valve/relay Output 24 Vac powered contact
EKEmergency heat relay Output 24 Vac powered contact
GFFan relay coil Output 24 Vac powered contact
ORCooling damper motor; changeover valve/relay Output 24 Vac powered contact
RVPower connection to transformer (internally
connected for heating and cooling)
Input
RC Power connection to cooling transformer Input
RH Power connection to heating transformer Input
W1 H1, R3 Stage 1 heating control Output 24 Vac powered contact
W2 H2, Y, R4 Stage 2 heating control Output 24 Vac powered contact
W3 Stage 3 heating control Output 24 Vac powered contact
Y1 C1, M Stage 1 cooling control Output 24 Vac powered contact
Y2 C2 Stage 2 cooling control Output 24 Vac powered contact
Y3
a
Stage 3 cooling control
a
Output 24 Vac powered contact
XX1,X2,C Common connection Input
T
Remote sensor
b
Input
L, C, H HSII control panel
OMomentary circuit, changeover
LED1,
LED2, COM
A,A1,A2,Z,C,L LEDs Annunciation
TExternal temperature readout, T relay
R1, R2 LO and HI speed fan relays
RS Cooling contactor
YMCompressor contactor
A1, A2, A3 Auxiliary relay Output Dry contact
CA1-CA5
Remote override
b
Input Low power
SET THERMOSTAT DIP SWITCHES
The thermostat DIP switches provide the thermostat
with an interface to the single zone HVAC system. See
Table 7 for DIP switch settings. The thermostat DIP switches
are located on the back of the thermostat. See Fig. 13. Set
the DIP switches for the desired thermostat features and the
system being controlled.
IMPORTANT: The thermostat configuration must match
the application, or the control logic will not function
properly.
TABLE 7—THERMOSTAT DIP SWITCH SETTINGS
Switch Setting Function
1ON
a
°F display
OFF °C display
2ON
a
12 hour clock display
OFF 24 hour clock display
3ON
a,b
Intermittent fan operation in occupied
period
OFF Continuous fan operation in occupied
period
4 Nonfunctional switch
5ON
a
Keyboard is used for programming
OFF Keyboard disabled, but can be used to
review program, perform overrides
and make clock changes.
a
Factory setting.
b
Q7300B,C,D,E,L: fan switch will override this switch
setting.
Q7300A,F,G: no override is available.