How to fix a Honeywell T7350 display that won't come on?
- DDavid OnealAug 22, 2025
If the display on your Honeywell Thermostat won't turn on, the thermostat might not be getting power. Check that the X terminal is connected to the system transformer and verify there's 24 Vac between the X and RH or RC terminals. If 24 Vac is missing: * Check if the circuit breaker is tripped and reset it if needed. * Check if the system fuse is blown and replace it if necessary. * Ensure the HVAC equipment power switch is in the On position. * Check the wiring between the thermostat and HVAC equipment, replacing any broken wires and tightening loose connections. If 24 Vac is present, continue troubleshooting.