T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
11 69-1331—5
5 Number of heating
stages.
Global 1, 2 Number of heating
stages found during
Automatic Discovery
mode.
0, 1, 2, 3 Select the number of
heating stages for this
application.
8 Number of cooling
stages (maximum for
W8635B is one).
Global 1, 2 Number of cooling
stages found during
Automatic Discovery
mode.
0, 1, 2 Select the number of
cooling stages for this
application.
9 Number of emergency
heat stages (only when
used with W8835 or
W8635B).
Global 1 Number of
emergency heating
stages.
0, 1, 2 Select the number of
emergency heat stages
for this application.
13 Adaptive Intelligent
Recovery™ (system
starts early so setpoint
is reached by start of
program period).
Global 0 Adaptive Intelligent
Recovery™ is
activated.
1 Conventional recovery
(system starts recovery
at period start time).
14 Temperature indication
scale (°F or °C)
Global 0 Temperature is
indicated in °F.
1 Temperature is indicated
in °C.
16 Clock format Global 0 12-hour clock format 1 24-hour clock format.
19 Fan overrun in heating
(not implemented for
gas/oil heat).
Global 0 0 seconds of fan
operation after
heating turns off.
1 90 seconds of fan
operation after heating
turns off.
20 Fan overrun in cooling. Global 0 0 seconds of fan
operation after
cooling turns off.
1 90 seconds of fan
operation after cooling
turns off.
25 Keypad lockout. Local 0 No lockout 1 1—Locks out all except
i, run, dst, and set
current day/time.
2—Locks out all except i,
run, dst, and set current
day/time.
(In all cases, the
combination to enter the
Installer Setup and the
Installer Test is
available.)
30 Minimum deadband
between heating and
cooling.
Global 3 Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C) to 10°F
(5 °C).
4 to 10 Heating and cooling
setpoints can be set no
closer than the chosen
value between 3° F and
10 °F (1.5 and 5 °C).
33 Minimum off time for
cooling and compressor.
Global 5 Five-minute minimum
off time for the
compressor.
0, 1, 2, 3,
4 or 5
Choose 0, 1, 2, 3, 4 or 5
minute minimum off time
for the compressor.
34 Maximum setpoint
range stop for heating.
Global 90°F
(32°C).
Heating setpoint
range can be set no
higher than 90°F
(30°C).
40°F
through
90°F
(4.5°C to
32°C).
Maximum setpoint range
stop can be set
anywhere between 40° F
and 90°F in 1°F (0.5°C)
increments.
35 Minimum setpoint range
stop for cooling.
Global 45°F
(7°C).
Cooling setpoint
range can be set no
lower than 45°F.
45°F
through
99°F (7°C
to 37°C).
Minimum setpoint range
stop can be set
anywhere between 45°F
and 99°F in 1°F (0.5°C.)
increments.
Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change) Description Scope
Default Setting
Other Options (Press or
key to change
Display Description Display Description

Other manuals for Honeywell T8635L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell T8635L and is the answer not in the manual?

Honeywell T8635L Specifications

General IconGeneral
BrandHoneywell
ModelT8635L
CategoryThermostat
LanguageEnglish

Related product manuals