T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
11 69-1331—5
5 Number of heating
stages.
Global 1, 2 Number of heating
stages found during
Automatic Discovery
mode.
0, 1, 2, 3 Select the number of
heating stages for this
application.
8 Number of cooling
stages (maximum for
W8635B is one).
Global 1, 2 Number of cooling
stages found during
Automatic Discovery
mode.
0, 1, 2 Select the number of
cooling stages for this
application.
9 Number of emergency
heat stages (only when
used with W8835 or
W8635B).
Global 1 Number of
emergency heating
stages.
0, 1, 2 Select the number of
emergency heat stages
for this application.
13 Adaptive Intelligent
Recovery™ (system
starts early so setpoint
is reached by start of
program period).
Global 0 Adaptive Intelligent
Recovery™ is
activated.
1 Conventional recovery
(system starts recovery
at period start time).
14 Temperature indication
scale (°F or °C)
Global 0 Temperature is
indicated in °F.
1 Temperature is indicated
in °C.
16 Clock format Global 0 12-hour clock format 1 24-hour clock format.
19 Fan overrun in heating
(not implemented for
gas/oil heat).
Global 0 0 seconds of fan
operation after
heating turns off.
1 90 seconds of fan
operation after heating
turns off.
20 Fan overrun in cooling. Global 0 0 seconds of fan
operation after
cooling turns off.
1 90 seconds of fan
operation after cooling
turns off.
25 Keypad lockout. Local 0 No lockout 1 1—Locks out all except
▲ ▼ i, run, dst, and set
current day/time.
2—Locks out all except i,
run, dst, and set current
day/time.
(In all cases, the
combination to enter the
Installer Setup and the
Installer Test is
available.)
30 Minimum deadband
between heating and
cooling.
Global 3 Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C) to 10°F
(5 °C).
4 to 10 Heating and cooling
setpoints can be set no
closer than the chosen
value between 3° F and
10 °F (1.5 and 5 °C).
33 Minimum off time for
cooling and compressor.
Global 5 Five-minute minimum
off time for the
compressor.
0, 1, 2, 3,
4 or 5
Choose 0, 1, 2, 3, 4 or 5
minute minimum off time
for the compressor.
34 Maximum setpoint
range stop for heating.
Global 90°F
(32°C).
Heating setpoint
range can be set no
higher than 90°F
(30°C).
40°F
through
90°F
(4.5°C to
32°C).
Maximum setpoint range
stop can be set
anywhere between 40° F
and 90°F in 1°F (0.5°C)
increments.
35 Minimum setpoint range
stop for cooling.
Global 45°F
(7°C).
Cooling setpoint
range can be set no
lower than 45°F.
45°F
through
99°F (7°C
to 37°C).
Minimum setpoint range
stop can be set
anywhere between 45°F
and 99°F in 1°F (0.5°C.)
increments.
Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change) Description Scope
Default Setting
Other Options (Press ▲ or
▼ key to change
Display Description Display Description