VISIONPRO® 8000 SMART THERMOSTAT
23 33-00096—04
405 Min. Heat Recovery
Ramp Rate
Off
1° F/hr to 20° F/hr
5° F/hr Commercial Off: The heating system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the heating system can recover at for a cold
day in your region. Default setting is 5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day in
your region to be associated with the Minimum
Recovery Ramp Rate. The thermostat will begin
recovery at the optimal time based on a calculated
ramp rate, allowing the system to recover on time
and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
405 Min. Heat Recovery
Outdoor Temp
Off
-20° F to 100°F
0° F Commercial Off: The heating system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the heating system can recover at for a cold
day in your region. Default setting is 5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day in
your region to be associated with the Minimum
Recovery Ramp Rate. The thermostat will begin
recovery at the optimal time based on a calculated
ramp rate, allowing the system to recover on time
and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes