VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04 26
408 Max. Cool Recovery
Ramp Rate
Off
1° F/hr to 20° F/hr
6° F/hr Commercial Off: The cooling system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a mild
day in your region. Default setting is 6° F / hour.
Set an Outdoor Temperature that is representative of
a mild day in your region to be associated with the
Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
408 Max. Cool Recovery
Outdoor Temp
Off
-20° F to 100°F
70° F Commercial Off: The cooling system will begin recovery at the
time that is scheduled.
When a Maximum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Maximum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a mild
day in your region. Default setting is 6° F / hour.
Set an Outdoor Temperature that is representative of
a mild day in your region to be associated with the
Maximum Recovery Ramp Rate.
The thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing the
system to recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature.
409 Adaptive Recovery
No
Yes
Yes Residential No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or cooling
recovery early to ensure that the temperature is
reached at the scheduled time. The thermostat will
adjust the start time of the equipment based on how
quickly the scheduled temperature was reached on
previous days. See page 51 for more information on
Adaptive Intelligent Recovery.
410 Minimum Cool
Setpoint
50° F to 99° F
50° F Both The user cannot set the temperature below this level.
410 Maximum Heat
Setpoint
40° F to 90° F
90° F Both The user cannot set the temperature above this level.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes