VERSAFLOW MAG 4000
www.honeywellprocess.com34-VF-25-51 iss.4 GLO May 18 US
2.8 Installation conditions
2.8.1 Inlet and outlet
2.8.2 Bends in 2 or 3 dimensions
Figure 2-6: Recommended inlet and outlet
1 Refer to chapter "Bends in 2 or 3 dimensions"
2 t 2 DN
INFORMATION!
Sensors of type VN02 up to DN10:
The inlet and outlet sections are enclosed inside the sensor.
Figure 2-7: Inlet when using 2 and/or 3 dimensional bends upstream of the flowmeter
Inlet length: using bends in 2 dimensions: t 5 DN; when having bends in 3 dimensions: t 10 DN
INFORMATION!
2 Dimensional bends occur in a vertical or
oror
or horizontal plane only, while 3 Dimensional bends
occur in both vertical and
andand
and horizontal plane.