6 Error search list
error No. Possible causes Measures
Actuator
spindle not
moving
1.1
1.2
1.3
1.4
1.5
Manual positioning is not in
zero position.
Compressed air is not in
contact with actuator.
Ruptured membrane.
Valve cone jammed.
Control force is too weak for the
valve.
Bring manual positioning into zero position
(see chapter 5.1)
Check compressed air system.
Exchange membranes.
See error search list for the valve.
Check dimension or contact manufacturer of
the overall system.
Actuator
spindle
moves jerkily
2.1
2.2
2.3
There is too little compressed
air.
Control regulator set incorrectly.
Valve cone has seized slightly
due to dirt particles.
Check compressed air system for damage
and sufficient flow.
Correction of the settings (see operating
manual control regulator).
See error search list for the valve.
High air
consumption
3.1
3.2
3.3
Membranes not pressed in
properly.
Seals worn.
Inflow conduits to actuator
leaking.
Re-tighten hexagonal nuts (18) until
membranes pressed in properly (4).
Exchange guide (10) and/or membranes (4).
Check inflow conduits for leaks and replace
or seal if necessary.
If the measures described above do not result in a satisfying outcome, the supplier / manufacturer must be