Enclosure Unit –
Rack Model
Dimensions
(H x W x D)
(with bezel)
10.4 x 19.1 x 32.977 in (265 x 485 x 835 mm)
Weight
(approximate)
Maximum
(one enclosure with 8
blades and 4 interconnects
installed)
300 lb (136 kg)
Minimum
(one enclosure without
blades and interconnects)
130 lb (59 kg)
Input Requirements
(per AC power supply)
Rated Line Voltage
90
–
132 VAC
180
–
264 VAC
Rated Input Current
9.3 A (at 100 VAC)
9.7 A (at 120VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)
Rated Input Frequency
47 to 63 Hz
BTU Rating
Maximum per power
supply
2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)
Power Specifications
To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL:
www.hp.com/go/bladesystem/powercalculator
Power Supply Output
(per power supply)
Rated Steady-State Power
800 W (at 100 VAC)
900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)
Maximum Peak Power
880 W (at 100 VAC)
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC)
System Inlet
Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m (1.8°F
per every 1000 ft) above sea level to a maximum
of 3050 m (10,000 ft), no direct sustained
sunlight. Maximum rate of change is 10°C/hr
(18°F/hr). The upper limit may be limited by the
type and number of options installed. System
performance may be reduced if operating with a
fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F)
maximum wet bulb temperature, non-
condensing.
QuickSpecs
HP BladeSystem c3000 Enclosure
Technical Specifications
DA - 12790 North America — Version 55 — December 10, 2013
Page 30