Check either Yes or No. If No, include comment or date.
Computer Room
Number Area or condition Yes No Comment or
Date
21. Are the input circuit breakers adequate for equipment
loads?
Safety
22. Is an emergency power shutoff switch available?
23. Is a telephone available for emergency purposes?
24. Does the computer room have a fire protection system?
25. Does the computer room have anti-static flooring
installed?
26. Do any equipment servicing hazards exist (loose ground
wires, poor lighting, and so on)?
Cooling
27. Can cooling be maintained between 5° C (41° F) and
40° C (104° F) up to 1,525 m (5,000 ft)? Derate 1° C/
305 m (1.8° F/1,000 ft) above 1,525 m (5,000 ft) and up to
3,048 m (10,000 ft).
Table Continued
32 System specifications