HP ProLiant DL380 Generation9 (Gen9)
c04375627 – DA – 15034 North America — Version 7 — February 17, 2015
System performance may be reduced if operating in the extended
ambient operating range or with a fan fault.
-30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr
(36°F/hr).
Minimum to be the higher (more moisture) of -12°C (10.4°F) dew point
or 8% relative humidity. Maximum to be the lower (less moisture) of
24°C (75.2°F) dew point or 90% relative humidity.
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing.
3050 m (10,000 ft). This value may be limited by the type and number
of options installed. Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
9144 m (30,000 ft). Maximum allowable altitude change rate is 457
m/min (1500 ft/min).
Listed are the declared A-Weighted sound power levels (LWAd) and declared average
bystander position A-Weighted sound pressure levels (LpAm) when the product is operating
in a 23°C ambient environment. Noise emissions were measured in accordance with ISO 7779
(ECMA 74) and declared in accordance with ISO 9296 (ECMA 109).
NOTE: The Listed sound levels apply to standard shipping configurations (Entry LFF, Entry,
Base, Base LFF and Performance models) additional options may result in increased sound
levels. The Base LFF model leverages our High Efficiency Fans, other models are shipping
with standard fan options.
CISPR 22; EN55022; EN55024; FCC CFR 47, Pt 15; ICES-003; CNS13438;
GB9254; K22;K24; EN 61000-3-2; EN 61000-3-3; EN 60950-1; IEC
60950-1
NOTE: Product conformance to cited product specifications is based on sample (type) testing,
evaluation, or assessment. This product or family of products is eligible to bear the
appropriate compliance logos and statements.
NOTE: The Listed sound levels apply to standard shipping configurations. Additional options
may result in increased sound levels.