2. User Interface
Continued
Description
Available settings
Default settings
In/Out settings
Load segments - Auto 
shutdown delay
[Disable] [0s] [1 s] [2 s]…[65354 s] 
During a power outage, this setting 
enables the UPS to turn off power to 
equipment connected to Group 1 and/or 
Group 2 outlets, or disables the action.  
This feature sheds non-critical loads in 
order to conserve battery power for critical 
loads connected to the primary group.
Group 1: Disable 
Group 2: Disable
Overload  
prealarm
[5%] [10%] [15%] [20%] ... [100%] [105%] 
Sets alarm for critical percentage of load 
where alarm overload occurs.
[105 %]
ON/OFF settings
Cold start [Disable] [Enable] 
Enables or disables the product to start 
on battery. The first cold start is always 
disabled.
Enable
Forced reboot [Disable] [Enable] 
If enabled and power returns during 
a shutdown sequence, the shutdown 
sequence will complete and there is a 10 
second delay prior to restart.
If disabled, shutdown sequence does not 
complete and restart occurs immediately.
Enable
Auto restart [Disable] [Enable] 
Enables or disables the UPS to restart 
automatically when power returns after a 
complete battery discharge.
Enable
Energy saving [Disable] [Enable] 
If enabled, the UPS will shutdown after 
five minutes if no load is detected on the 
output.
Disable
Sleep mode [Disable] [Enable] 
If enabled, LCD and communication stays 
on 1h and 30 min after UPS turns off. 
If disabled, LCD and communication will 
turn off immediately after the UPS turns 
off.
Disable
Remote command [Disable] [Enable] 
If enabled, shutdown or restart commands 
from software are allowed.If disabled, shut-
down or restart commands from software 
are not allowed.
Enable
Battery settings
Automatic battery test [No test] [Every day] [Every week] [Every 
month] 
Available only if Battery Charge mode is 
set to constant charge.
Every week  
(in constant charge)  
otherwise following EBM
Low battery  
warning
[10%] [20%] [30%] [40%] [50%] [60%] 
[70%] [80%] [90%] 
The alarm occurs when the value set  
for the low battery capacity warning is 
reached.
20%
Restart battery level [10%] [20%] [30%] [40%] [50%] [60%] 
[70%] [80%] [90%] [100%] 
If set, automatic restart occurs only when 
the percentage of battery charge you 
specify is reached.
0%
Battery charge mode [EBM cycling] [Constant charge] EBM cycling
ERM number  
setting
[0] [1] [2] [3] [4] 
Using standard ERM, the UPS automatically 
detects the number of connected ERMs.
ERM automatic detection,  
otherwise 0
Deep discharge protec-
tion
[Yes] [No]  
If set to Yes, the UPS automatically pre-
vents the battery from deep discharge by 
adapting the end of back-up time voltage 
threshold.
Yes