5. Maintenance
5.1 Troubleshooting
Operation status  Possible cause
Action
Batteries disconnected
The UPS does not recognize  
the internal batteries
If the condition persists, contact your 
service representative
The batteries are disconnected
Verify that all batteries are properly 
connected. If the condition persists, 
contact your service representative.
Overload Power requirements exceeds the 
UPS capacity (greater than 105 %  
of nominal)
Remove some of the equipment 
from the UPS. The UPS continues  to 
operate, but may shutdown if  
the load increases. The alarm resets 
when the condition becomes  
inactive.
End of battery life 
The end of the battery life is 
reached.
Contact your service representative 
for battery replacement.
Event  An UPS event occurs
Example: 
The RPO contact has been activated  
to shutdown the UPS and now  
prevents restart.
For this event, set the contact back 
to its normal position and press the  
 button to restart.
UPS fault
The UPS has an internal fault The UPS does not protect the  
equipment. 
Note: Record the alarm message 
and the UPS Serial Number, then 
contact your service representa-
tive.
5.2 Updating the UPS rmware
To update the UPS rmware, see the HP website (http://www.hp.com/go/rackandpower).