Specify Grounding Requirements
50
Check that the braid contact connection points are free of paint or other insulating material and treated
with a contact enhancement compound (similar to Burndy Penetrox).
Cable trough top
Ground connection of
panel ground wire
(inside trough)
Hex bolt,
bellville washer and nut
Open end at panel
Hex bolt,
bellville washer and nut
Grounding braid to
computer equipment
Drill trough
as required
Cable trough
Ground wire
Cable trough top and
cable trough is used
as grounding system
6/1/97