8
15. Does the input voltage correspond to equipment specifications?
16 Does the input frequency correspond to equipment
specifications?
17. Are lightning arrestors installed?
18. Is power conditioning equipment installed?
No. Area or condition Yes No
19. Is there a dedicated branch circuit for equipment?
20. Is the dedicated branch circuit less than 250 feet (72.5 meters)?
21. Are the input circuit breakers adequate for equipment loads?
Safety
No. Area or condition Yes No
22. Is there an emergency power shut-off switch?
23. Is there a telephone available for emergency purposes?
24. Is there a fire protection system in the computer room?
25. Is antistatic flooring installed?
26. Are there any equipment servicing hazards?
27. Are the proper tools and installation equipment available?
Cooling
No. Area or condition Yes No
28. Can cooling be maintained between 54
° and 86° F
(20
° and 30° C)?
29. Can temperature changes be held to less than 10
° C per hour?
30. Can humidity level be maintained between 40% and 60%?
31. Are air conditioning filters installed?
Table 2