Chapter 8 Troubleshooting and Maintenance Shenzhen Hpmont Technology Co., Ltd.
-56- HD09 Series User Manual V1.1
Fault Fault reasons Counter-measures
E0007
Stall overvoltage
Bus voltage is too high
The setting of stall overvoltage is
too low
Please check power input or the
function of brake
Set the value of stall overvoltage
properly (F19.19)
E0008
Fault of power
module
Short circuit between phases
output
Short circuit to the ground
Output current is too high
Power module is damaged
Please check the connection and
connect the wire properly
Please check the connection and
connect the wire properly
Please check the connection and
mechanism
Please contact the supplier for
repairing
E0009
Heatsink overheat
Ambient temperature is too high
Inverter external ventilation is not
good
Fan fault
Fault occurs to temperature
detection circuit
Please use inverter with higher power
capacity
Improve the ventilation around the
inverter
Replace the cooling fan
Please seek technical support
E0011
CPU fault
CPU abnormal
Please detect at power on after
completely power outage
Please seek technical support
E0012
Parameters auto-
tuning fault
Parameter auto-tuning is time out
Please check the motors connection
Input the correct motor parameters
(F08.01 - F08.03)
Please seek technical support
E0013
Contactor is not
actuated
Contactor fault
Fault of control circuit
Replace the contactor
Please seek technical support
E0014
Fault of current
detection circuit
Current detection circuit is
damaged
Please contact the supplier for
repairing
E0016
Fault of output phase
Output phase disconnectionor
loss
Heavy imbalance of inverters
three-phase load
Please check the connection between
inverter and motor
Please check the quality of motor
E0017
Inverter overload
Acceleration time is too short
Improper setting of V/f curve or
torque boost leads to over current
Mains supply voltage is too low
Motor load is too high
Adjust acceleration time (F03.01)
Adjust V/f curve (F09.01 - F09.06) or
torque boost (F09.07, F09.08)
Please check mains supply voltage
Please use inverter with proper power
rating

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the hpmont HD09-2S1P5G and is the answer not in the manual?

hpmont HD09-2S1P5G Specifications

General IconGeneral
Brandhpmont
ModelHD09-2S1P5G
CategoryInverter
LanguageEnglish

Related product manuals