LP-179 Rev. 6.7.16
13
Performance Specications for Phoenix Models
BTU/Hr Eciency
Temperature Rise in Degrees Fahrenheit (F) and Celsius (C)
(°F) 40 50 60 70 80 90 100 110 120 130 140
(°C) 22 28 33 39 44 50 56 61 67 72 78
100,000
96%
GPH 298 240 202 173 152 136 123 110 101 94 88
LPH 1128 908 765 655 575 515 466 416 382 356 333
130,000
GPH 384 309 260 222 195 175 158 141 130 120 112
LPH 1454 1170 984 840 738 662 598 534 492 454 424
160,000
GPH 470 378 317 271 238 213 192 173 159 147 137
LPH 1779 1431 1200 1026 901 806 727 655 602 556 519
199,000
GPH 582 468 392 335 294 263 237 213 196 181 169
LPH 2203 1772 1484 1268 1113 996 897 806 742 685 640
Table 3 - Recovery on Rating Plate is based at 94% Thermal Eciency at 70
o
Fahrenheit rise, as required by ANSI
Figure 4 - Water Heater Dimensions - NOTE: All Dimensions Are Approximate
Performance Equations
Rated Input x .9
GPM = Temp Rise (
o
F) x 500 GPH = GPM x 60