1 3 No Enable
CAN
network
/ / /
... ... ... ... ...
CAN
network
... ... ...
7 1 7 No Enable
CAN
network
/ / /
8 1 8 Yes Enable
CAN
network
/ / /
The table uses 8 smart cooling products in CAN teamwork as an example.
1. Teamwork group no.: A maximum of four groups, with the same teamwork control number,
can be assigned (1ā4) for one teamwork networking.
2. Smart cooling product address: In a teamwork control group, each smart cooling product
address (1-32) must be unique, and the smart cooling product with minimum address is the
master smart cooling product.
3. Networking mode: The networking mode set on the screen must be consistent with the actual
networking mode.
4. Enable teamwork CAN resistor: Set the parameter if CAN teamwork is used. Set the parameter
to ON for the first and eight smart cooling products.
5. Number of smart cooling products in this group: Indicates the number of precision smart
cooling products in a group. The value is an integer ranging from 1 to 32.
6. Number of running smart cooling products in this group: Specifies the number of running
NetCol8000-As in a group. The value ranges from 1 to the number of NetCol8000-As in the
group.
7. Rotation function: Enable the active and standby smart cooling products to work alternately.
This function is recommended when the heat load is even.
1. Set the control mode based on the actual configuration of T/H sensors.
2. If a differential pressure switch is configured, set Indoor fan control type to Pressure diff ctrl.
Configuring Initial Parameters
9.3