34
Startup Process
9.2
Choose Maint > Wizard Startup to
enter wizard startup.
Open the Service Expert app.
Tap StartUp > Offline Activation on APP
After tapping Yes, the barcode and the
verification code are shown on the screen.
Start
Tap Start on the home screen.
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Yes on
Wizard
Startup screen
to enter wizard
startup.
Go to step 2
Refrigerant is fully charged?
No
Tap No on Wizard Startup screen to exit
wizard startup.
Yes
Charge the remaining amount of
refrigerant from low-pressure needle
valve.
1. First startup flowchart
Tap Enter. The screen turns to Wizard
Startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home
screen.
If there is no water supply,
clear the humidifier
commissioning item when
wizard startup
commissioning. After
Wizard startup, lift the
low liquid level detector.
After at least 5 seconds,
choose Running > Device
Details > Humidifier to
check that Low liquid
level states is Triggered.
Choose Running > Device
Details > Humidifier >
Advanced to check that
Humidifier pump control
states is On, the
humidifier is functional.
Success
2. Wizard startup flowchart
Success
Success
Success
Success
Outdoor fan commissioning
Electric heater
commissioning
Cooling system
commissioning
Humidifier commissioning
Indoor fan commissioning
Commissionin
g interrupted
(Handle the
fault by
referring to
the tips
displayed on
the home
screen.
Perform
wizard startup
after the
handling.)
Start
End
Precautions
Yes
No
No
Fail
Fail
Fail
Fail
Yes
Fail
Select commissioning
items