NO TE
For ease of the SUN2000 installation on the mounting bracket, cable connecting at the
bottom, and future maintenance, it is recommended that the clearance from the bottom
be between 600 mm and 730 mm. For further questions regarding clearance, consult
local technical support engineers.
The clearance from the bottom must meet the requirements on the bending radius of
the AC output power cables.
If multiple SUN2000s need to be installed and the clearance is
sucient, install
them in horizontal mode. The triangle, back-to-back, and close-to-wall installation
modes are not recommended. For triangle, back-to-back, and close-to-wall
installation modes, you need to prepare air
baes to isolate air intake from air
exhaust.
Figure 4-5 Horizontal installation mode (recommended)
Figure 4-6 Triangle installation mode (not recommended)
(1) Air
bae
NO TE
Stacked installation is not allowed.
SUN2000-(250KTL, 280KTL, 300KTL, 330KTL) Series
User Manual 4 Installation
Issue 07 (2023-06-30) Copyright © Huawei Technologies Co., Ltd. 31