SUN2000-(3KTL-10KTL)-M1
User Manual
Issue 02
Date 2020-11-20
HUAWEI TECHNOLOGIES CO., LTD.

Table of Contents

Other manuals for Huawei SUN2000-3KTL-M1

Questions and Answers

  • J
    Joshua PhillipsSep 23, 2025
    What does optimizer fault mean on Huawei Controller?
    • R
      Rachel SullivanSep 23, 2025
      If your Huawei Controller indicates an optimizer fault, it means the optimizer is either offline or faulty. To get more information, go to the optimizer information screen to view the fault details.
  • A
    Andrea CoffeyAug 25, 2025
    How to troubleshoot grid overvoltage on Huawei Controller?
    • A
      Angela MyersAug 25, 2025
      A grid overvoltage alarm on your Huawei Controller indicates that the grid voltage exceeds the upper threshold. Try these steps: 1. If the alarm is occasional, it could be a temporary grid issue. The SUN2000 should recover automatically once the grid stabilizes. 2. If the alarm persists, verify that the grid voltage is within the acceptable range. If it's not, contact your local power operator. If it is within range, you can adjust the grid overvoltage protection threshold using the mobile app, SmartLogger, or NMS, but only with the consent of the local power operator. 3. Also, check for peak voltage issues on the power grid; if the problem persists, contact the power operator.
  • J
    jeremy44Aug 25, 2025
    What to do if Huawei Controller reports grid loss?
    • R
      Randall HeathAug 26, 2025
      If the Huawei Controller displays a grid loss alarm, it means a power grid outage has occurred, or the AC circuit is disconnected, or the AC switch is off. The alarm should clear automatically once the power grid recovers. You can also check if the AC circuit is disconnected or if the AC switch is turned off.
  • E
    Eric OwenAug 27, 2025
    How to fix high string input voltage on Huawei Controller?
    • A
      Ashley LewisAug 27, 2025
      The high string input voltage on your Huawei Controller indicates that the PV array is not properly configured. Too many PV modules are connected in series, causing the PV string open-circuit voltage to exceed the maximum operating voltage. To resolve this, reduce the number of PV modules connected in series until the PV string open-circuit voltage is within the acceptable range. The alarm should disappear once corrected.
  • A
    Alicia NunezSep 23, 2025
    What does Grid-tied/ Off-grid Controller Abnormal mean on Huawei Controller?
    • J
      John ThomasSep 23, 2025
      The 'Grid-tied/ Off-grid Controller Abnormal' alarm on your Huawei Controller indicates that the inverter is failing to communicate with the Smart Backup Box, or that an unrecoverable fault has occurred on a circuit inside the Smart Backup Box. To troubleshoot: 1. Send a shutdown command on the app. Turn off the AC output switch, DC input switch, and battery switch. 2. Check whether the power cable and RS485 cable between the Smart Backup Box and the inverter are normal. 3. After 5 minutes, turn on the battery switch, AC output side, AC output switch, and DC input switch. 4. If the alarm persists, contact your dealer or Huawei technical support.
  • K
    kwilsonSep 13, 2025
    What does 'Battery abnormal' mean on my Huawei Controller?
    • T
      Taylor BerrySep 13, 2025
      If your Huawei Controller is showing a 'Battery abnormal' message, it indicates a fault with the battery itself. Here's what to check: 1. If the fault indicator on the battery is steady on or blinking, contact the battery dealer. 2. Verify that the battery enabling, power, and communications cable connections are correct, and that the communications parameters are consistent with the RS485 configurations of the inverter. 3. Ensure the battery auxiliary power switch is turned on.
  • K
    Katherine ValenciaSep 12, 2025
    What to do if Huawei Controller upgrade failed?
    • A
      Andrew CollinsSep 12, 2025
      If the Huawei Controller displays 'Upgrade failed or version mismatch', it means the upgrade process was not completed successfully. Try performing the upgrade again. If it fails repeatedly, contact your dealer or Huawei technical support.
  • R
    Rebecca ToddSep 12, 2025
    What causes grid voltage imbalance in Huawei Controller?
    • S
      Sandra RichardsSep 12, 2025
      A grid voltage imbalance alarm on the Huawei Controller indicates that the difference between grid phase voltages exceeds the upper threshold. Here's how to handle it: 1. If the alarm occurs occasionally, the power grid may be temporarily abnormal. The SUN2000 should recover automatically. 2. If the alarm persists, check whether the power grid voltage is within the acceptable range. If not, contact the local power operator. 3. If the alarm lasts for a long time, check the AC output power cable connection. 4. If the AC output power cable is correctly connected, yet the alarm persists and affects the energy yield of the PV plant, contact the local power operator.
  • W
    William RobinsonSep 4, 2025
    What does abnormal grounding mean on a Huawei Controller?
    • R
      Renee RushSep 4, 2025
      Abnormal grounding on the Huawei Controller indicates that the neutral wire or PE cable of the inverter is not connected, or the output mode set for the inverter is inconsistent with the cable connection mode. Power off the inverter first (turn off the AC output switch and DC input switch, and wait for a period of time). Then: 1. Check whether the PE cable for the inverter is connected properly. 2. If the inverter is connected to a TN power grid, check whether the neutral wire is properly connected and whether the voltage of the neutral wire to ground is normal. 3. After powering on the inverter, check whether the output mode set for the inverter is consistent with the output cable connection mode.
  • S
    smithjonathanSep 1, 2025
    Why is the grid frequency unstable on my Huawei Controller?
    • K
      Kristina MeyerSep 2, 2025
      An unstable grid frequency alarm on the Huawei Controller indicates the power grid frequency change rate doesn't meet local power grid code requirements. Here's what you can do: 1. If the alarm is occasional, it may be a temporary grid issue, and the SUN2000 should recover automatically. 2. If the alarm persists, check whether the power grid frequency is within the acceptable range. If not, contact the local power operator.

Summary

About This Document

Overview

Describes the SUN2000 inverter's scope, features, functions, and safety precautions.

Intended Audience

Identifies personnel for whom this document is applicable, including installers and users.

Symbol Conventions

Defines the meaning of symbols used in the document, such as Danger, Warning, and Caution.

Change History

Safety Information

General Safety

Provides essential safety statements, warnings, and guidelines for operating and maintaining the equipment safely.

Personnel Requirements

Specifies the necessary qualifications, training, and experience for personnel involved in installation and maintenance.

Electrical Safety

Outlines critical electrical safety precautions, including grounding, AC/DC power handling, and cable connections.

Installation Environment Requirements

Defines the necessary environmental conditions for safe and optimal installation and operation of the SUN2000.

Mechanical Safety

Covers safety precautions related to mechanical operations, such as using ladders and handling heavy objects.

Commissioning

Details the procedures and precautions for the initial power-on and parameter setting of the equipment.

Maintenance and Replacement

Provides safety guidelines for performing maintenance tasks and replacing components on the SUN2000.

Overview

Product Introduction

Introduces the SUN2000 inverter, its functions, and the different models covered in the document.

Appearance

Details the physical components and indicators of the SUN2000, including port descriptions and LED indicators.

Label Description

Explains the various labels and markings on the equipment, such as warning labels and serial number information.

Working Principles

Describes the internal workings of the SUN2000, including circuit diagrams and operating modes.

Storage

Installation

Checking Before Installation

Guides users on inspecting outer packing materials and package contents before proceeding with the installation.

Tools

Lists the essential tools required for the installation of the SUN2000, categorized into installation and PPE tools.

Determining the Installation Position

Covers environment and space requirements, including ventilation, material compatibility, and clearance for installation.

Moving the SUN2000

Provides instructions and precautions for safely moving the SUN2000 unit from its packaging to the installation location.

Installing the Mounting Bracket

Details the procedure for installing the mounting bracket, including wall-mounted and support-mounted methods.

Electrical Connections

Installation Preparation

Outlines preliminary steps and component descriptions necessary before making electrical connections.

Connecting the PE cable

Explains the procedure for securely connecting the protective earth (PE) cable, including important safety notes.

Connecting the AC Output Power Cable

Details how to connect the AC output power cable, including precautions and stripping requirements.

Installing DC input power cables

Provides instructions for connecting DC input power cables, including warnings about voltage and polarity.

(Optional) Connecting Battery Cables

Describes the procedure for connecting battery cables, including prerequisites and safety warnings.

Install the Smart Dongle

Guides on installing different types of Smart Dongles (WLAN-FE and 4G) for communication.

(Optional) Connecting the Signal Cable

Explains how to connect signal cables, including COM port pin definitions and networking scenarios.

Commissioning

Checking Before Power-On

Provides a checklist of items to verify before powering on the SUN2000 for the first time.

SUN2000 power-on

Details the step-by-step procedure for powering on the SUN2000, including checking indicators and switches.

Man-Machine Interaction

App Commissioning

Guides on using the FusionSolar app for device commissioning, including downloading, registration, and layout setup.

Parameters Settings

Explains how to configure various parameters like energy control, AFCI, and IPS checks via the app or system.

SmartLogger Networking Scenario

Describes how to set up networking scenarios involving SmartLogger for data collection and monitoring.

Maintenance

SUN2000 Power-Off

Details the procedure and safety precautions for safely powering off the SUN2000 unit.

Routine Maintenance

Outlines the recommended schedule and methods for performing routine checks and maintenance on the SUN2000.

Troubleshooting

Provides a comprehensive list of common faults, their causes, severity, and solutions for diagnosing and fixing issues.

Handling the Inverter

Removing the SUN2000

Describes the steps and precautions required to safely remove the SUN2000 from its mounting bracket.

Packing the SUN2000

Provides instructions on how to properly pack the SUN2000 unit for storage or transportation.

Disposing of the SUN2000

Gives guidance on the proper disposal of the SUN2000 unit at the end of its service life.

Technical Specifications

SUN2000 Technical Specifications

Presents detailed technical data for the SUN2000 inverters, including efficiency, input, and output parameters.

Optimizer Technical Specifications

Lists the technical specifications for the optional Smart PV Optimizer, covering its performance and input/output characteristics.

Grid Code

Device Commissioning

Access Device Commissioning Screen

Details how to access the device commissioning interface on the FusionSolar app, with methods for connected and unconnected states.

Connect to Solar Inverter WLAN and Log In

Explains the steps to establish a WLAN connection to the SUN2000 and log in as an installer user.

Resetting Password

Rapid Shutdown

Locating Insulation Resistance Faults

Acronyms and Abbreviations

Huawei SUN2000-3KTL-M1 Specifications

General IconGeneral
ModelSUN2000-3KTL-M1
TypeString Inverter
Max. DC Input Voltage600 V
MPPT Voltage Range90 V - 560 V
Rated AC Output Power3000 W
Max. AC Output Power3300 W
Nominal AC Voltage220 V / 230 V / 240 V
AC Voltage Range180 V - 280 V
AC Output Frequency50 Hz / 60 Hz
Max. Efficiency98.6%
MPPT Trackers2
DC Inputs per MPPT1
Max. Input Current per MPPT11 A
Operating Temperature Range-25°C to +60°C
Cooling MethodNatural Convection
Protection DegreeIP65
Max. DC Input Power4500 W
CommunicationRS485
Dimensions (W x H x D)365 mm x 365 mm x 156 mm