SUN2000-(33KTL-A, 36KTL, 42KTL)
User Manual
Issue
07
Date
2018-05-04
HUAWEI TECHNOLOGIES CO., LTD.

Other manuals for Huawei SUN2000-33KTL-A

Questions and Answers

  • M
    Michael PonceAug 17, 2025
    Why is my Huawei Inverter showing an abnormal grid voltage?
    • L
      Luis SparksAug 17, 2025
      This alarm may occur accidentally if the power grid is temporarily abnormal. The Huawei SUN2000 automatically recovers after detecting that the power grid becomes normal. This is due to the grid voltage being below the specified lower threshold.
  • J
    Jessica WoodsAug 20, 2025
    How to fix high DC input voltage on Huawei SUN2000-33KTL-A Inverter?
    • V
      Veronica WoodAug 20, 2025
      This issue occurs when the PV array is not properly configured. Reduce the number of PV modules connected in series to PV strings 1 and 2 until the open-circuit voltage is less than or equal to the maximum inverter input voltage. After the PV array configuration is corrected, the Huawei SUN2000 alarm disappears.
  • E
    Elizabeth CobbAug 22, 2025
    What causes abnormal grounding in Huawei Inverter?
    • P
      Phillip SanchezAug 22, 2025
      This issue may be due to the neutral wire or PGND cable not properly connected to the inverter, or the Huawei SUN2000 output side does not connect to an isolation transformer when the PV string output is grounded. Check that the neutral wire or PGND cable properly connects to the inverter. If the PV string output is grounded, check that the SUN2000 output side connects to an isolation transformer.
  • B
    browncurtisAug 25, 2025
    What does abnormal grid frequency mean on a Huawei Inverter?
    • W
      wrochaAug 26, 2025
      If the alarm occurs accidentally, the power grid may be abnormal temporarily. The Huawei SUN2000 automatically recovers after detecting that the power grid becomes normal. This happens because the actual grid frequency is higher than the standard requirement for the local power grid.
  • G
    Gregory CannonAug 27, 2025
    How do I troubleshoot low insulation resistance on a Huawei SUN2000-33KTL-A?
    • J
      Julia CaldwellAug 27, 2025
      Check the impedance between the PV string and the PGND cable. If a short circuit occurs, rectify the fault. If you are sure that the impedance is less than the default value in a cloudy or rainy environment, log in to the SUN2000 app, SmartLogger, or NMS and set Insulation resistance protection. A short circuit occurs between the PV string and the PGND cable.
  • P
    Paige AyalaAug 30, 2025
    What does abnormal DC circuit mean for Huawei SUN2000-33KTL-A?
    • K
      Kayla DouglasAug 30, 2025
      The Huawei SUN2000 detects its external working conditions in real time. After the fault is rectified, the SUN2000 automatically recovers. This issue occurs when the SUN2000 input is disconnected accidentally, or the PV string output power changes sharply because the PV string is shielded from sunlight.
  • E
    Edgar WardSep 1, 2025
    What causes a DC arc fault in my Huawei SUN2000-33KTL-A?
    • S
      Steven BerrySep 1, 2025
      Check whether the PV string cable is in poor contact or with open circuits. If yes, reconnect the cable. The PV string cable is in poor contact or with open circuits.
  • I
    ian64Sep 4, 2025
    Why is my Huawei SUN2000-33KTL-A showing a cabinet overtemperature warning?
    • K
      Kylie MillerSep 4, 2025
      Check the ventilation and ambient temperature of the Huawei SUN2000 installation position. If the ventilation is poor or the ambient temperature exceeds the upper threshold, improve the ventilation and heat dissipation. If the ventilation and ambient temperature both meet requirements, contact Huawei technical support. This issue occurs when the SUN2000 is installed in a place with poor ventilation, the ambient temperature exceeds the upper threshold, or the internal fan works abnormally.
  • S
    Stephanie ThomasSep 6, 2025
    What to do if string 1-8 reversed on Huawei Inverter?
    • S
      susan04Sep 6, 2025
      Check whether the PV string is reversely connected to the Huawei SUN2000. If yes, wait until the solar irradiance declines at night and the PV string current reduces to below 0.5 A. Then, turn off the two DC switches and correct the PV string connection. Check whether the number of PV modules connected in series to the SUN2000 is small. If yes, increase the number. The PV string is reversely connected or only a few PV modules are connected in series to the PV string, and therefore the end voltage is lower than that of other PV strings.
  • K
    Kelly PughSep 9, 2025
    How to resolve AFCI self-check failure on Huawei Inverter?
    • T
      Tina WarnerSep 9, 2025
      Turn off the AC output switch and DC input switch. Then turn on the AC output switch and DC input switch after 5 minutes. If the fault persists, contact Huawei technical support. Disable the AFCI function if you are sure not to use it. AFCI check fails.

Summary

Safety Precautions

System Installation

Tools for Installation

Lists required tools for installation and cabling.

Wall-mounting the SUN2000

Requirements and procedures for wall mounting.

Installing the Mounting Bracket

Steps for installing the bracket.

Installing the SUN2000

Steps for mounting the SUN2000 onto the bracket.

Support-mounting the SUN2000

Requirements and procedures for support mounting.

Connecting Cables

Connecting the Ground Cable

Prerequisites and procedure for ground cable connection.

Connecting AC Output Power Cables

Prerequisites, specs, and procedures for AC cables.

Connecting DC Input Power Cables

Prerequisites, specs, and procedures for DC cables.

Connecting Communications Cables

Procedures for RS485, PLC, and FE communication cables.

System Commissioning

Powering On the SUN2000

Prerequisites and procedure for system startup.

Powering Off the SUN2000

Procedure for safely shutting down the system.

Man-Machine Interactions

Maintenance

Routine Maintenance

Guidance on regular checks for optimal operation.

Troubleshooting Alarms

Lists alarms, causes, and solutions.

Technical Specifications

Huawei SUN2000-33KTL-A Specifications

General IconGeneral
ModelSUN2000-33KTL-A
TypeString Inverter
Rated Output Power33 kW
Max. DC Input Voltage1100 V
Input Voltage Range200 V - 1000 V
Number of MPPT Trackers2
Max. Apparent AC Power33 kVA
Rated AC Power33 kW
Rated AC Voltage400 V
Rated Grid Voltage400 V
Rated Grid Frequency50 Hz / 60 Hz
Max Efficiency98.6%
Protection LevelIP65
Operating Temperature Range-25°C to 60°C
Cooling MethodNatural Cooling