EasyManua.ls Logo

Huawei SUN2000-300KTL-H0 - Page 50

Huawei SUN2000-300KTL-H0
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NO TE
The cable diameter must comply with local cable standards.
The factors that aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
Table 5-2 Cable description (S indicates the conductor cross-sectional area of the AC output cable,
and S
p
indicates the conductor cross-sectional area of the PE cable)
No. Cable Type Conductor
Cross-Sectional
Area
Outer
Diameter
Source
1 DC input
power cable
PV cable that meets
the 1500 V standard
4–6 mm
2
5–7.8 mm Prepared by
the
customer
2 RS485
communicat
ions cable
Outdoor shielded
twisted pair cable that
meets the local
standard
0.25–1 mm
2
One or
two
communi
cations
cables: 4–
11 mm
Three
communi
cations
cables: 4–
8 mm
Prepared by
the
customer
3 PE cable Single-core outdoor
copper cable and M10
OT/DT terminal
S
p
≥ S/2 - Prepared by
the
customer
4 Tracking
system
power cable
Three-core outdoor
copper cable with two
layers of protection
and M4 OT terminal
10 mm
2
15–18 mm Prepared by
the
customer
5 AC output
power cable
(single-core)
(Recommended)
Single-core outdoor
cable and M12 OT/DT
terminal
Copper cable:
S: 120–150
mm
2
S
p
≥ S/2
Aluminum
alloy cable or
copper-clad
aluminum
cable:
S: 150–400
mm
2
S
p
≥ S/2
14–40 mm Prepared by
the
customer
SUN2000-(250KTL, 280KTL, 300KTL, 330KTL) Series
User Manual 5 Electrical Connections
Issue 07 (2023-06-30) Copyright © Huawei Technologies Co., Ltd. 43

Table of Contents

Related product manuals