EasyManuals Logo

Huawei SUN2000-40KTL-M3 User Manual

Huawei SUN2000-40KTL-M3
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #132 background imageLoading...
Page #132 background image
Figure I-1 PV string access detection
No. Parameter Description Remarks
1 PV string access
detection
PV string access detection is set to Disable by
default. After the inverter connects to the power grid
properly, set this parameter to Enable.
-
2 Startup current When the current of all connected PV strings reaches
the preset value, the PV string access detection
function is enabled.
NOTE
Startup current setting rules:
Startup current = I
sc
(S
tc
) x 0.6 (rounded up). For details
about I
sc
(S
tc
), see the PV module nameplate.
Default startup current (5 A): applicable to the scenarios
where the short-circuit current I
sc
(S
tc
) is greater than 8 A
for the monocrystalline and polycrystalline PV modules.
This
parameter
is
displayed
when PV
string
access
detection
is set to
Enable.
3 Startup current for 2-
in-1 detection
When the current of a PV string reaches Startup
current for 2-in-1 detection, the PV string is
automatically identied as 2-in-1.
The default value is recommended.
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual I PV String Access Detection
Issue 18 (2024-03-10) Copyright © Huawei Technologies Co., Ltd. 122

Table of Contents

Other manuals for Huawei SUN2000-40KTL-M3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-40KTL-M3 and is the answer not in the manual?

Huawei SUN2000-40KTL-M3 Specifications

General IconGeneral
Max. Efficiency98.7%
European Efficiency98.4%
Max. Input Voltage1100 V
MPPT Operating Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated Output Power40000 W
Rated AC Voltage400 V
Rated AC Frequency50 Hz / 60 Hz
Adjustable Power Factor Range0.8 leading - 0.8 lagging
Total Harmonic Distortion (THD)<3%
DC Reverse-Polarity ProtectionYes
AC Overcurrent ProtectionYes
DC Surge ProtectionType II
AC Surge ProtectionType II
Insulation MonitoringYes
Residual Current MonitoringYes
DC SwitchYes
Protection ClassIP66
Operating Temperature Range-25°C to +60°C
Relative Humidity (Operating)0% - 100%
CoolingNatural Convection
Max. Apparent AC Power44000 VA
AC Voltage Range320 V - 480 V
Operating Altitude4000 m
DisplayLED Indicators
CommunicationRS485, WLAN
Weight43 kg
Max. DC Power60000 W

Related product manuals