Mounting Structure Requirements
The mounting structure for the inverter must be reproof. Do not install the
inverter on ammable building materials to avoid personal injury or property
loss caused by re or other reasons.
Ensure that the installation surface is solid enough to bear the weight of the
inverter to avoid personal injury or property loss caused by the collapse of the
mounting structure or other reasons.
In residential areas, do not install the inverter on a drywall or wall made of
similar materials which have a weak sound insulation performance because
the inverter generates noise during operation.
Installation Angle Requirements
The inverter can be wall-mounted or support-mounted. The installation angle
requirements are as follows:
Install the inverter vertically or at a maximum back tilt of 15 degrees to
facilitate heat dissipation.
Do not install the inverter at forward tilted, excessive backward tilted, side
tilted, horizontal, or upside down positions.
Figure 4-1 Installation angle
Installation Clearances
Reserve enough clearances around the inverter to ensure sucient space for
installation and heat dissipation.
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 4 Installation
Issue 18 (2024-03-10) Copyright © Huawei Technologies Co., Ltd. 28

Table of Contents

Other manuals for Huawei SUN2000-40KTL-M3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-40KTL-M3 and is the answer not in the manual?

Huawei SUN2000-40KTL-M3 Specifications

General IconGeneral
Max. Efficiency98.7%
European Efficiency98.4%
Max. Input Voltage1100 V
MPPT Operating Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated Output Power40000 W
Rated AC Voltage400 V
Rated AC Frequency50 Hz / 60 Hz
Adjustable Power Factor Range0.8 leading - 0.8 lagging
Total Harmonic Distortion (THD)<3%
DC Reverse-Polarity ProtectionYes
AC Overcurrent ProtectionYes
DC Surge ProtectionType II
AC Surge ProtectionType II
Insulation MonitoringYes
Residual Current MonitoringYes
DC SwitchYes
Protection ClassIP66
Operating Temperature Range-25°C to +60°C
Relative Humidity (Operating)0% - 100%
CoolingNatural Convection
Max. Apparent AC Power44000 VA
AC Voltage Range320 V - 480 V
Operating Altitude4000 m
DisplayLED Indicators
CommunicationRS485, WLAN
Weight43 kg
Max. DC Power60000 W