Item 1 kVA 2 kVA 3 kVA
Input
power
factor
(100%
resistive
load)
> 0.99
Startup
voltage
120–280 V AC
Generator
input
capacity
Minimum 1.5 times the UPS rated capacity
3.4 Bypass Input Electrical Specications
Table 3-4 Bypass Input Electrical Specications
Item
1 kVA 2 kVA 3 kVA
Bypass voltage
tolerance
170 V –264 V AC
Bypass frequency
tolerance
47–53 Hz or 57–63 Hz
Bypass overload
capability
110%–120%, 30 minutes
120%–130%, 10 minutes
130%–150%, 1 minute
Input mode One mains input
NO TE
The upper and lower thresholds of bypass voltage tolerance are congurable on the LCD.
3.5 Output Electrical Specications
Table 3-5 Output electrical specications
Item
1 kVA 2 kVA 3 kVA
Rated capacity 1000 VA/800
W
2000 VA/1600
W
3000 VA/2400
W
Output power factor (PF) 0.8
UPS2000-A-(1 kVA-3 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 26