6 Operations
6.1 Checking Before Power-On
AC power cable colors comply with local regulations.
The input and output are not short-circuited.
Cables and terminals are securely connected.
Battery cables and terminals are correctly connected, and voltages comply
with industry standards.
The UPS is properly connected to battery strings.
Power cables and signal cables are correctly labeled.
Cables are neatly routed and securely bound according to requirements.
The equipment is installed and cables are routed in ways that facilitate
modication, capacity expansion, and maintenance.
The equipment is properly grounded.
The voltage dierence between the neutral wire and the ground cable is less
than 5 V AC.
The input voltage range for the mains to start the UPS is 175–270 V AC. The
input voltage range for batteries to start the UPS is (Number of batteries x
10.8 V DC) to (Number of batteries x 14 V DC).
UPS2000-A-(1 kVA-3 kVA)
User Manual 6 Operations
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 74

Other manuals for Huawei UPS2000-A-1KTTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTL and is the answer not in the manual?

Huawei UPS2000-A-1KTTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A-1KTTL
CategoryUPS
LanguageEnglish

Related product manuals