EasyManuals Logo

Huawei UPS2000-A-1KTTL User Manual

Huawei UPS2000-A-1KTTL
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
Figure 6-4 Setting the battery capacity
5. Start the UPS to inverter mode.
Hold down the ON/MUTE button on the front panel for over 5 seconds to
make the UPS transfer to inverter mode output. The default value is 220 V.
Figure 6-5 LCD display after the UPS starts to inverter mode
NO TE
To prevent triggering overload protection, start the loads with higher power and then
loads with lower power.
6.3 Shutting Down the UPS
Normal Mode
If the UPS is originally in normal mode, hold down OFF/ENTER for over 2 seconds
will enable the UPS to enter the standby mode or bypass mode (if set or enabled
before).
Battery Mode
Hold down OFF/ENTER for over 2 seconds to turn o the UPS in battery mode.
6.4 Transferring to Bypass Mode
When the input power supply is normal and the UPS is started in normal mode,
hold down ON/MUTE and SELECT both for 5 seconds to enable the UPS enter the
bypass mode. If the input voltage exceeds the acceptable range, the UPS will not
enter the bypass mode.
UPS2000-A-(1 kVA-3 kVA)
User Manual 6 Operations
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 77

Other manuals for Huawei UPS2000-A-1KTTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTL and is the answer not in the manual?

Huawei UPS2000-A-1KTTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A-1KTTL
CategoryUPS
LanguageEnglish

Related product manuals