Item 1 kVA 2 kVA 3 kVA
Inverter overload capability When the ambient temperature is 0–35°C:
105%–110%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 10 min.
110%–130%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 1 min.
130%–150%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 3s.
> 150%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after no more than 0.5s.
When the ambient temperature is 35–40°C:
105%–110%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 5 min.
110%–130%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 30s.
130%–150%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after 1.5s.
> 150%: The UPS transfers to bypass
mode (from normal mode) or shuts
down automatically (from battery mode)
after no more than 0.5s.
Dynamic voltage transient
±5%
Average frequency tracking
rate
1 Hz/s
Transfer time Transferring
from normal
mode to
battery mode
0
Bypass to
ECO or ECO
to bypass
4 ms (100% resistive load)
UPS2000-A-(1 kVA-3 kVA)
User Manual 3 Technical Specications
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 28