No. Item Acceptance Criterion
4 Cable labels Labels are neatly attached to both ends of
each cable, and the information on the
labels is concise and understandable.
5 Ground cable connection The ground cable is securely connected to
the equipment room ground bar. Measure
the resistance between the UPS ground
cable and the equipment room ground bar,
which must be less than 0.1 ohm.
6 Distances between cable
ties
Distances between cable ties are the same,
and no burr exists.
7 Operating environment The inside and outside of the cabinet are
free from conductive dust or other foreign
matter.