Alar
m ID
Caus
e ID
Nam
e
Seve
rity
Clear
ance
Mod
e
Trigger
Condition
Impact on the
System
Solution
66 3 Outp
ut
overl
oad
Critic
al
This
alarm
must
be
manu
ally
cleare
d.
In battery
mode, this
alarm is
generated
when the
load
exceeds
the rated
load.
In normal
mode,
when the
bypass
input is
normal,
this alarm
is
generated
when the
UPS
transfers
to normal
mode
three
times
within 20
minutes
after the
UPS
transfers
from
normal
mode to
bypass
mode.
In normal
mode,
when the
bypass
input is
abnormal,
this alarm
is
generated
when the
UPS
In battery
mode, the
UPS transfers
to no output.
If the UPS
transfers from
normal mode
to bypass
mode three
times within
20 minutes,
the UPS is
locked in
bypass mode.
In normal
mode, the
UPS transfers
to no output.
Possible cause: The
load exceeds the rated
load capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a larger-
capacity UPS.
UPS2000-A-(1 kVA-3 kVA)
User Manual 5 Setting Control Panel
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 70

Other manuals for Huawei UPS2000-A-1KTTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTL and is the answer not in the manual?

Huawei UPS2000-A-1KTTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A-1KTTL
CategoryUPS
LanguageEnglish

Related product manuals