Alar
m ID
Caus
e ID
Nam
e
Seve
rity
Clear
ance
Mod
e
Trigger
Condition
Impact on the
System
Solution
159 1 On
batte
ry
Mino
r
The
alarm
is
auto
matic
ally
cleare
d.
The UPS
transfers to
battery mode.
The UPS
transfers to
battery mode.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains input. If the
mains input is
abnormal, wait for
the mains to
recover.
Possible cause: The
battery self-check is
in progress.
Measure: Check
whether the battery
self-check is in
progress.
9E 1 On
bypa
ss
Mino
r
This
alarm
is
auto
matic
ally
cleare
d.
The
inverter is
not
started.
The load
power
exceeds
the rated
inverter
loading
capability.
The
temperatu
re exceeds
the rated
temperatu
re.
If the bypass is
abnormal, the
UPS may power
o.
Check whether
other alarms are
generated. If other
alarms are
generated, clear
them.
If there are no other
alarms, start the
inverter manually.
9F 1 On
batte
ry
Mino
r
This
alarm
is
auto
matic
ally
cleare
d.
The mains
input is
abnormal.
When the UPS
works in battery
mode, the UPS
may power o if
the batteries are
abnormal.
Check the mains input.
If the mains input is
abnormal, wait until
the mains input
recovers.
UPS2000-A-(1 kVA-3 kVA)
User Manual 5 Setting Control Panel
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 72

Other manuals for Huawei UPS2000-A-1KTTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A-1KTTL and is the answer not in the manual?

Huawei UPS2000-A-1KTTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A-1KTTL
CategoryUPS
LanguageEnglish

Related product manuals