Item Expected Result Measures Maintenance
Interval
Battery
connection
reliability
1. Each battery
terminal is
connected
reliably. (When
battery strings
are powered
o, check the
reliability of
each terminal
in the order
from positive
terminals to
negative
terminals.)
2. The tightening
torque of each
battery screw
meets the
requirements
of the battery
manufacturer.
(A torque
wrench is used
for checking
the torque.
After checking
that the
battery screws
meet the
requirements,
mark the
screws for later
check.)
1. Rectify any
abnormal
connection.
2. If the fault
persists,
contact
Huawei
technical
support.
Yearly
UPS2000-A-(1 kVA-3 kVA)
User Manual 8 Routine Maintenance
Issue 17 (2024-01-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 87