UPS2000-A-(6 kVA-10 kVA)
User Manual
4 Control Panel
Copyright © Huawei Technologies Co., Ltd.
69
Na
me
LCD
Function
Value
Range
Preset
Value
Remarks
Out
put
volt
age
lev
el
Set the
system
output
voltage
level. After
you change
the voltage
level, the
upper
bypass
voltage
threshold is
restored to
the default
value 15%.
Standar
d
version:
220 V,
230 V,
and 240
V
Professi
onal
version:
208 V,
220 V,
230 V,
and 240
V
220 V
The value
is
configura
ble only
after the
inverter
shuts
down.
Out
put
freq
uen
cy
syst
em
Set the
system
output
frequency
level. If the
value is
Automatic,
the
power-on
bypass
frequency
ranges
from 45 Hz
to 55 Hz,
and the
system
output
frequency
is 50 Hz; if
the
power-on
bypass
frequency
ranges
from
(excluding
55 Hz) 55
Hz to 65
50 Hz, 60
Hz, and
AUT
(automatic)
50 Hz
The value
is
configura
ble only
after the
inverter
shuts
down.