UPS2000-G1-(1 kVA–3 kVA)
User Manual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Used to prevent the electrostatic
discharge (ESD) from damaging a
board or other electrostatic
sensitive devices (ESSDs) when
you insert or remove a board or
hold an ESSD.
Used to crimp the OT terminals
and JG terminals with a large
cross-sectional area of 10 mm
2
, 16
mm
2
, 25 mm
2
, or 35 mm
2
.
Installation Environment
The UPS installation environment should meet the following requirements:
The temperature and humidity are within the range of 0–40°C and 0%–95% respectively.
Install the UPS in an environment with good ventilation and free of dust, volatile gas,
salt, and corrosive materials. Keep the UPS far away from water, heat source, flammable
and explosive substances. Avoid direct sunlight.
The optimal operating temperature for batteries is 20–30°C. Operating at temperatures lower
than 20°C will shorten the battery backup time, and operating at temperatures higher than
30°C will shorten the battery lifespan.
Installation Clearance
The UPS installation clearance should meet the following requirements:
Maintain a clearance of at least 60 mm from the front panel and rear panel of the UPS to
the wall or adjacent equipment.
Keep the air inlets unobstructed on the front panel and rear panel of the UPS to facilitate
ventilation and heat dissipation. Otherwise, the UPS internal temperature will rise, which
will shorten the lifetime of the UPS.