UPS2000-G1-(1 kVA3 kVA)
User Manual
A Technical Specifications
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
30
Item
UPS2000-G1-1
kVA
UPS2000-G1-3
kVA
Frequency
Normal mode: The UPS output phase is
the same as the bypass input phase when
synchronized.
Battery mode: 50 Hz / 60 Hz (tolerance
±0.5%)
Waveform
Sine wave (The total harmonic distortion
[THD] at linear loads is less than 3%.)
Switchover time
4 ms for the UPS to transfer from the
normal or battery mode to the bypass
mode
0 ms for the UPS to transfer from the
normal mode to the battery mode
Overload duration
105%130% rated load: The UPS
transfers to the bypass after 60 seconds.
130%150% rated load: The UPS
transfers to the bypass after 30 seconds.
150% rated load: The UPS works
properly for 300 ms.
Output mode
Three IEC-compliant C13 sockets are
provided.
Enviro
nment
Operating temperature
040°C
Storage temperature
20°C to +55°C (After the UPS has been
stored or transported at 20°C, do not
install it until its temperature has been
kept at 0°C for four hours.)
Humidity
0%95% (non-condensing)
Altitude
≤ 1500 m
When the altitude is greater than 1500 m,
the output capacity should be derated as
required by the IEC 60146-1-2.
Acoustical noise
< 45 dB
Certifi
cation
Electromagnetic compatibility
(EMC)
Complying with the EN/IEC 60240-2
Safety and regulatory
Complying with the EN/IEC 60240-1

Related product manuals