Installation Preparations
1
Clearances and Cabinet Description (1200 kVA)
Clearances and Cabinet Description (1600 kVA)
1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise,
personal injury or equipment damage may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
4. This document describes the installation procedure for a single UPS. For details about how to install a parallel system,
contact Huawei technical support.
Model Weight Dimensions (H x W x D)
UPS5000-H-1200K-NTN < 1600 kg 2200 mm x 1600 mm x 1000 mm
UPS5000-H-1600K-NTN < 2300 kg 2200 mm x 2400 mm x 1000 mm
Inductor cabinet < 1100 kg 2000 mm x 600 mm x 1000 mm
Item
1200 kVA
1600 kVA
Remarks
Mains input
Mains input current (A)
2229
2972
Connection method:
Crimped DT terminal
Bolt specifications:
L1/L2/L3/U/V/W/PE: M12 x 45 mm
(47 N·m)
Battery +/
-/PE: M16 x 55 mm (120 N·m)
Equipotential ground point: M6 x 20 mm
(4.5 N·m)
NOTE:
The currents listed in the table are measured at a rated voltage
of 380 V.
If the top cabling component and bottom cabling cabinet are
not configured, copper bars need to be prepared for the mains
input, bypass input, and output, which cannot be directly
connected using cables. (Huawei does not provide copper bars
or connector boxes.)
If they are configured, refer to the
recommended cable specifications in the user manual.
The battery input can be connected only using cables.
Bypass input
Bypass input current (A)
1823
2431
Output
Output current (A)
1823
2431
Battery input (lead
-acid
battery)
Nominal battery discharge current (A)
2660
3546
Maximum battery discharge current (A)
3185
4247
Recommended cross
-
sectional area
(mm
2
)
-
6 x
(2 x 240)
8 x (2 x 240)
2 x 240
Battery input (
SmartLi)
Nominal battery discharge current (A)
2493
3324
Maximum battery discharge current (A)
3192
4172
Recommended cross
-sectional area (mm
2
)
For details, see the IEC
-60364-5-52
specifications and
SmartLi
User Manual
.
Equipotential ground point
Recommended cross
-sectional area (mm
2
)
16
Installation
Clearances
Issue: 01
Date: 2021-10-13
Installation
Clearances
Cabinet Description
Cabinet Description
Inductor
cabinet
Power
cabinet 1
Power
cabinet 2
Bypass
cabinet
Bypass modules
Rectifiers
Fan power switch QS1-4
Main switch QF of the
inductor cabinet
Fans
Surge protection boxes
Control module
Intelligent detection card
Bypass control module
Power modules
SPDs and
SPD switches
Inductor
cabinet
UPS cabinet
Bypass fan PSU
Bypass modules
Rectifiers
Main switch QF of the inductor cabinet
Fans
Surge protection boxes
Control module
Intelligent detection card
Bypass control module
Power modules
SPDs and
SPD switches
Bypass fan power supply unit (PSU)
Fan power switch QS1-4
UPS5000-H-(1200 kVA-1600 kVA) Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire)

Other manuals for Huawei UPS5000-H Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-H Series and is the answer not in the manual?

Huawei UPS5000-H Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-H Series
CategoryUPS
LanguageEnglish

Related product manuals