Problem Cause Solution
Flow-Sync not reading correctly Controller congured incorrectly Set correct ow sensor size and
type at controller.
Turbulent ow at sensor Insure that straight pipe is on either
side of ow meter.
Frequent false alarms Station settings too sensitive Increase overow percentage (and
underow if available).
Wide range of ows for a single
station
Increase overow and underow
percentages, and delay interval.