38
be completely isolated from the supply gas. If the
air or nitrogen break-in gas will adversely affect the
downstream system, it too must be isolated.
Since all industrial gases are dangerous to human
life, it must be ensured that there are no leaks in the
system that would compromise the safety of personnel
or property.
Leak detection may be accomplished with a ‘bubble
test’ or an electronic sniffer that determines the amount
of the gas in the surrounding air.
Any leaks that are found must be fi xed at once, before
standard operation of the compressor is resumed.
DAILY STARTUP CHECKLIST
1. Check the oil level in the crankcase.
2. Drain liquid from the air receiver and moisture
traps (if equipped).
3. Turn on cooling water (if not regulated by the
system).
4. Start compressor per previous section.
5. Check system pressure.
6. Check oil pressure.
7. Check relief valves for proper operation.
8 . Check control system for proper operation.