General safety information
LVU-CD-40
en(us)
Page 11 / 68
BeWa LVU-CD-40 4035823a en-us 2016-01-08.doc 2016-01-08
Proper/Designated Use
Use the unit only for the application described in the following.
The LowViscosity Unit LVU is used for two-stage offline filtration, with solid
particle contamination and free water being removed from diesel fuel. The
degree of water separation is > 95 % as per ISO CD 16332 and the
dewatering rate is 50 l/h at 5 % water in the diesel. The limit of application is
obtained at a maximum of 10 % free water.
DANGER
Unacceptable fluid temperature
Risk of bodily injury due to burns
Observe the maximum fluid temperature of <
50°C and at least 10°C below the flash point
of the fluid used.
DANGER
Dry running of the pump
Risk of bodily injury due to burns
Ensure that the pump does not run dry.
NOTICE
Impermissible operating media.
The unit will be destroyed.
The unit may only be used in combination with diesel, .biodiesel
B0 … B100 or fuel oil.
Proper or designated use of the product extends to the following:
observing all instructions contained in these operating instructions.
adhering to maintenance work.