WIRE SIZE
NORTH AMERICA
• The minimum wire size for systems that require a 40A GFCI is # 8/3 c/w ground (also referred to as # 8 gauge / 4 conductor).
• The minimum wire size for systems that require a 50A GFCI is # 8/3 c/w ground (also referred to as # 8 gauge / 4 conductor).
EUROPE
Standards for amperage breakers may vary from country to country in the CE controlled area. Please consult your local
installer for advice on breaker level and wire specificaons. Some examples are below:
Breaker of 13A –wire must be 1.5 mm2
Breaker of 16A—wire must be 2.5 mm2
Breaker of 20A—wire must be 4.0 mm2
Breaker of 32A—wire must be 6.0 mm2
NOTE: Please consult your applicable electrical codes related to the size of conductors as they may vary from what is stated
above. Take into consideraon the length of cable as well and increase as required.