33
12.10
If the unit experiences a fault, the “FAULT ICON” will flash to indicate it. Clicking on this
icon will take you to the real-time fault/fault record. This page can display up to 20
real-time faults and 50 historical faults. Once the fault has been resolved, the icon will
disappear.
ERROR CODES
E05 HIGH VOLTAGE PROTECTION
E09 COMMUNICATION FAILURE
E12 COMPRESSOR TEMP TO HIGH
E14 WATER TEMP SENSOR FAILURE
E16 EVAPORATOR TEMP SENSOR FAIL
E18 COMPRESSOR TEMP SENSOR FAIL
E21 AMBIENT TEMP SENSOR FAIL
E29 SUCTION TEMP SENSOR FAIL
i
If a fault occurs please note down the error code and then call technical support
1300 769 904
12.10 LEGIONELLA CONTROLL STRATERGY
In order to maintain disinfection of stored water, the heat pump controller and sensor postions
are designed that a minimum 45% of stored water will reach a temperature of 60°C daily.
However should you require it is possible to set an additional disinfection cycle being to 70°C
weekly. This heating is done by from current temp to 70°C by the element & held for 32min.
In the functions menu select
FACTORY PARMETERS then enter
PASSCODE: ?????? cycle through to
PARMETER 66 click to change
parmeter from 0 TO 1
ADD A LEGIONELLA BOOST CYCLE