EasyManua.ls Logo

Hypontech HPT-30K Series - Technical Parameter

Hypontech HPT-30K Series
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27 User Manual
9. TECHNICAL PARAMETER
MODEL
HPT-30K
HPT-33K
HPT-36K
HPT-40K
HPT-50K
INPUT / DC
Max. PV Power / Wp
49500
54000
60000
65000
Max. Input Voltage /
V
1100
MPP Voltage Range /
V
150-1000
Full Load MPP
Voltage Range / V
330-900
330-900
380-900
430-900
500-900
Min. DC Voltage /
Start Up Voltage / V
150/180
Nominal DC-Input
Voltage / V
620
Max. Input Current /
A
30/30/30
30/30/30/30
Max. DC Short Circuit
Current / A
45/45/45
45/45/45/45
No. of Independent
MPPT Inputs
3
4
No. of PV Strings per
MPPT
2
OUTPUT / AC
Rated Power / W
30000
33000
36000
40000
50000
Max. Apparent AC
Power / VA
33000
36300
39600
44000
55000
Rated Grid Voltage /
Vac
380/400 | 3 / 3L-N-PE or 3 / 3L-PE
Rated Power
Frequency / Hz
50/60