4.3.2.1 Basic settings
The following table shows the factory-default settings.
Setting Default Description
Heat Mode 2 Stage Heat
Set heating mode. Options:
No heating
1 Stage Heat
2 Stage Heat
Stg 1 HP, Stg 2 Aux
2 Stage Heat Pump
Cool Mode 1 Stage Cool
Set cooling mode. Options:
No Cooling
1 Stage Cool Only
2 Stage Cool Only
1 Stage Heat Pump
2 Stage Heat Pump
Boiler Heating Boiler/Aux Backup
Set boiler heating mode. Options:
None
Boiler/Aux Backup
Boiler Only
Temperature Fahrenheit
Set temperature format. Options:
Fahrenheit
Celsius
Tankless Off
Set tankless water heater mode.
Toggles On / Off
4.3.2.2 Advanced settings
Certain Advanced settings are available only after modes have been set up in Basic settings.
Setting Default Description
Pump Enabled On Set to off, if no pump connected to AHU.
Pump Exercise Interval
(hours)
24
Circulates water in coil every xx (set hours); set
per local code
65