EasyManuals Logo

IBC CX 150 User Manual

Default Icon
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Secure joints using appropriate solvent cement to bond the respective pipe material
(Canada: CPVC cement approved under ULC-S636, in accordance with its
manufacturer instructions; USA: PVC (ASTM D2564), or PVC/ABS (D2235) - Use
transition glue anywhere that PVC and CPVC are joined. Follow the cement
manufacturer’s instructions closely when joining various components. For PP,
connections shall be secured using approved retainer clips supplied by the respective
PP manufacturer.
Check that vent connections are liquid and pressure tight. Prior to firing the boiler, and
before any of the venting run is concealed by the building construction, test the exhaust
joints under fan pressure with the vent blocked, using a soap and water solution. The
installer must fill the condensate trap prior to testing.
Coat all joints with an approved leak test solution just as you would joints in a gas line,
and make sure there are no leaks. We suggest attaching a tag on the vent line near the
condensate drain tee with the type of test, the date and the installer’s name.
Re: venting passage through ceiling and floor:
Confirm material meets local codes including fire stopping requirements.
Check the local jurisdiction on the minimum initial length of pipe that should be
exposed or accessible for inspection.
Follow the local codes for pipe clearances - no IBC requirements.
Ensure that piping is liquid and pressure tight.
3.7.4.1 Air intake and exhaust vent length allowance
Warning
Follow all installation instructions supplied by the piping and fitting manufacturer.
The maximum vent lengths shown are separate for the intake and exhaust. For example, for a
maximum vent length of 100 ft, the exhaust can travel a maximum of 100 equivalent ft and the
intake can travel a maximum of 100 equivalent ft. Any unused vent lengths used on one side
can not be added to the other. Equivalent feet of any elbows, termination kits, or flexible pipe
must be subtracted from the maximum length using the table below:
Intake/Exhaust CX150 CX199
2-inch rigid pipe 50 ft (max.) Not permitted
3-inch rigid pipe 170 ft (max.) 100 ft (max.)
90° elbow Allow 8 feet for each 90° elbow
90° long sweep elbow Allow 5 feet for each 90° elbow
45° elbow Allow 3 feet for each 45° elbow
PP 87-90° elbow Allow 8 feet for each 87-90° elbow
2-inch Stainless
Sidewall Terminal (P-
Not permitted Not permitted
28
Section: Installation

Table of Contents

Other manuals for IBC CX 150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC CX 150 and is the answer not in the manual?

IBC CX 150 Specifications

General IconGeneral
BrandIBC
ModelCX 150
CategoryBoiler
LanguageEnglish

Related product manuals